KL731A
KILSEN KA700 Series addressable optical smoke detector
- Remote signalling capabilities
- Easy soft addressing (1-125)
- SMD technology
- Reliable communication protocol
- Full diagnostic self testing
Related products
At a glance
Product overview
The KL700A series detectors use an enhanced protocol that ensures the overall integrity and error free operation of the system. All detectors are compatible with a standard base and support the connection of a remote indicator.
KL710A heat detector
An alarm is raised when the temperature exceeds a fixed temperature or the rate-of-rise of temperature is exceeded. It is used where a fire could cause an abrupt elevation of the temperature, or where smoke of controlled combustion, aerosols, etc. do not allow the use of any other type of detector.
KL731A/B optical smoke detectors
The Tyndall optical effect of smoke in a chamber is used to detect a fire. It is used in areas where possible combustible materials, like plastics, polystyrene, PVC, etc., generate visible smoke.
For installations with false ceilings or black ceilings where detectors should not be visible, this device is also available in black with a black detector base.
The addressable optical detector is available in either white or black colours.
For installations with false ceilings or black ceilings where detectors should not be visible, this device is also available in black with a black detector base.
The addressable optical detector is available in either white or black colours.
KL735A dual detector
Dual technology (one photoelectric and two heat sensors) is used for accurate detection of various types of fires. The heat detection is based on a fixed and rate-of-rise response whilst the photoelectric sensor uses the Tyndall optical effect.
User friendly
Detectors are identified by soft addressing. The address is stored in flash memory and eliminates the risk of addresses being changed without authorization. Other addressable accessories include conventional zone monitors, various in- and output units, sounder controllers, manual call points and isolators.
Details
- Remote signalling capabilities
- Easy soft addressing (1-125)
- SMD technology
- Reliable communication protocol
- Full diagnostic self testing
- Full range: Optical and Heat and Dual detectors (optical/heat)
- Full range of supporting I/O units and accessories
- EN54 approved and CPR certified
Technical specifications
| General | ||
|---|---|---|
| Status indication |
Red (dual LED, alarm)
|
|
| Compatibility |
Kilsen addressable fire systems
|
|
| Alarm levels |
Configurable
|
|
| Connectivity |
2-wire loop
|
|
| Addressing method |
Electronic
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
Loop powered
|
|
| Operating voltage |
22 to 38 VDC
|
|
| Current consumption |
350 µA (quiescent @ 38 VDC)
<11 mA (in alarm)
|
|
| Detection | ||
|---|---|---|
| Detection principle |
Optical, light scatter
|
|
| Monitoring |
Alarm threshold
Contamination level
Continuously self-checking
|
|
| Coverage area |
60 to 80 m²
|
|
| Output | ||
|---|---|---|
| Output quantity |
1
|
|
| Output type and rating |
Remote indicator
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
45 x 99 mm (H x Ø)
|
|
| Net weight |
107 g
|
|
| Colour |
White (RAL 9010-P)
|
|
| Mounting type |
Base mount
Wall mount
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-10 to +60°C
|
|
| Storage temperature |
-10 to +70°C
|
|
| Relative humidity |
0 to 95% noncondensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP42
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RoHS 3
WEEE
|
|
| Certification |
CPR
|
|
| Standards |
EN54-7
|
|
Downloads
All downloadsDatasheet
Certificates
Installation sheet
CPD / CPR
Other EU certificate
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.