3000-026

Additional detector set for 3000-015 system
  • Seperate transmitter and receiver unit certified to Exd
  • Separate fire and fault relays per detector
  • Range 5 to 80m, configurable per set of detectors
  • Integral laser alignment in receiver
  • Low current consumption
View all

At a glance

3000-026 is an additional detector set for the 3000-115 End-to-End Explosive Proof Beam Smoke Detector. 3000-026 comprises of an infrared transmitter and a receiver, both of which are ATEX-certified for use in Group 2 hazardous areas.

Operation

The Transmitter head emits a narrow beam of infra-red light to an associated Receiver head. Once smoke crosses through and thus obscures the IR beam path, the signal strength at the Receiver drops below a preset level which in turn results in an alarm condition.

It has been designed so that it can be installed by a single Engineer, with its laser assisted alignment method combined with easy to use alignment LEDs offering visual feedback. Integrated laser alignment aid can be activated at the Controller.

It also has a feature which allows for the Transmitter to be powered from the Controller by wiring directly, thus reducing the number of power supplies required.

Details

  • Seperate transmitter and receiver unit certified to Exd
  • Separate fire and fault relays per detector
  • Range 5 to 80m, configurable per set of detectors
  • Integral laser alignment in receiver
  • Low current consumption
  • Programmable sensitivity and fire/fault delay
  • Contamination compensation for dust and building movement
  • Transmitter can be powered from controller
  • ATEX, IECEx, EN54:12, VdS Approved
  • Light cancellation technology

Technical specifications

General
Status indication
Receiver: Alignment LEDs for single person alignment
Reset time
Power Down: >20 s
Electrical
Operating voltage
12 to 36 VDC +/-10%
Current consumption
8 mA (per transmitter)
Detection
Optical wave length
850 nm
Physical
Physical dimensions
172 x 149 x 190 mm (incl. bracket), Transmitter/Receiver
Net weight
3.7 Kg (incl. bracket)
Mounting type
Wall mount
Environmental
Operating temperature
-20 to 55°C, noncondensing
Relative humidity
93%, noncondensing
Environment
Exd
IP rating
IP66, Transmitter/Receiver
Regulatory
Certification
CENELEC/ATEX
Fire and Fault Relay Contacts
2A @ 30Vdc resistive
Housing Material
Transmitter/Receiver Aluminium Alloy LM25, red
Bracket Steel, red
Parts List
Transmitter (clear lens), receiver (dark lens), fixing kit, two brackets
Alarm & Operation Thresholds
Delay to Alarm/Fault Min: 2sec; Typ: 10sec; Max: 30sec (selectable in 1sec steps)
Laser Time-out Min: 1min; Typ: 5min; Max: 59min (selectable in 1min steps)
Response Sensitivity/Threshold Min: 25%; Typ: 35%; Max: 60% (selectable in 1% steps)
Certifications
EN54:12 and ATEX Ex II 2GD
Ex db op is IIC T6 Gb
Ex tb IIIC T85C Db