Skip to main content

AD218SS-0100

Alarmline II Digital LHD Cable 218°C (424°F), Stainless Steel braid, 100 m (328 ft.)
  • Detection along total cable length
  • Simple maintenance free installation
  • Suitable for use in hazardous areas
  • RoHS Compliant
View all

At a glance

General

The AD218SS-0100 is a Digital Linear Heat Detection (LHD) cable with a 218°C (424°F) fixed temperature activation rating. It has a Stainless Steel over silicon outer sheath offering increased mechanical protection.

The AD range of digital sensor cables provides a very simple fixed temperature heat detection system which can be used in many applications where other forms of detection are not suitable.

Operation

The AD range of digital LHD cables contains a pair of twisted, low resistance, tri-metallic conductors sheathed with advanced temperature sensitive polymers. The cable operates by softening the insulation of the conductors, the tension of the twisted conductors then causes the two cores to fuse together. The sensor cable provides a simple switch operation which when used with a combination of end-of-line (EOL) monitoring and alarm trigger resistors can signal an alarm to any fire monitoring equipment through any monitored input i.e. conventional detection zone or addressable interface unit.

Location Control Unit

Additional to the LHD sensor cable, an optional digital location control unit which monitors the sensor cable and can identify along the length of the sensor cable where an alarm condition has occurred, is also available.

Cable fixings for all applications

A range of 'edge' ,'A' , 'P' , and 'T' clips allow the cable to be properly installed. The clips provide heat insulation as well as holding the cable at the correct distance from cable trays, steel works, ceilings and walls.

Details

  • Detection along total cable length
  • Simple maintenance free installation
  • Suitable for use in hazardous areas
  • RoHS Compliant

Technical specifications

Electrical
Operating voltage
0 to 70 VAC, 0 to 100 VDC
No. of cable cores
2
Insulation rating 5 kV tested protective outer coat
Conductor
Resistance
90 Ω/km (27.4 Ω/1000 ft.)
Capacitance
<85 pf/m (<26 pf/ft.)
Inductance
<2.00 μH/m (<0.61 μH/ft.)
Physical
Physical dimensions
5.5 mm x 100 m (0.216 in. x 328 ft.) (Ø x L)
Net weight
10.75 kg (23.7 lb.)
Shipping weight
13.55 kg (29.87 lb.)
Colour
Green
Mounting type
Cable mount
Bend radius 63.5 mm (2.5 in.) min., extended to 127 mm (5 in.) for low temperature environments
Material Silicon rubber with stainless steel braid
Environmental
Operating temperature
-40 to 170°C (-40 to 338°F) (Ambient)
218°C (424°F) (Alarm)
Relative humidity
0 to 100% noncondensing
Environment
Indoor
Outdoor
Regulatory
Certification
CE