TCC-0001
Ex. IS sounder, 24 VDC, red
- Approved by ATEX, IECEx
- Group I MI Ex ia I Ma
- Group II IGD Ex ia IIC T6 Ga, Ex ia IIIC T85˚C Da
- Zones 0, 1, 2, 20, 21 & 22
- Conforms to: EN 60079-0:2012 + All:2013 (IEC 60079-0:2011) EN-60079-11:2012 + (IEC 60079-11:2011)
Related products
At a glance
IS Sonos sounder
The IS electronic sounder has been approved for use in potentially explosive atmospheres for Group I (Mining) & Group II (Above Ground) applications and incorporates a high Ingress Protected IP66 enclosure.
The sounder unit incorporates a two stage alarm option and has a total of 32 selectable tones, selectable via a dip switch on the PCB and produces up to 105 dB at 1 meter.
A specially designed time saver base enables quick and easy installation of this unit with no extra cabling to be made to the head of the unit.
Connections are made to the base during the initial wiring phase which results in a faster more reliable installation. The sounder head simply twists & clicks into the pre-fixed base on commissioning avoiding any additional wiring & connections.
Further details can be found on the installation sheet’ This unit must be used in conjunction with an approved Zener Barrier or Galvanic Isolator. The characteristics should not exceed Uo: 28 V, Io: 93 mA, Po: 660 mW, Ci: 0, Li 0. The minimum value of Uo should not drop below 23.6 V and the minimum value of Io should not drop below 50 mA.
The sounder unit incorporates a two stage alarm option and has a total of 32 selectable tones, selectable via a dip switch on the PCB and produces up to 105 dB at 1 meter.
A specially designed time saver base enables quick and easy installation of this unit with no extra cabling to be made to the head of the unit.
Connections are made to the base during the initial wiring phase which results in a faster more reliable installation. The sounder head simply twists & clicks into the pre-fixed base on commissioning avoiding any additional wiring & connections.
Further details can be found on the installation sheet’ This unit must be used in conjunction with an approved Zener Barrier or Galvanic Isolator. The characteristics should not exceed Uo: 28 V, Io: 93 mA, Po: 660 mW, Ci: 0, Li 0. The minimum value of Uo should not drop below 23.6 V and the minimum value of Io should not drop below 50 mA.
Applications:
Fire, security, process control and general signalling
Details
- Approved by ATEX, IECEx
- Group I MI Ex ia I Ma
- Group II IGD Ex ia IIC T6 Ga, Ex ia IIIC T85˚C Da
- Zones 0, 1, 2, 20, 21 & 22
- Conforms to: EN 60079-0:2012 + All:2013 (IEC 60079-0:2011) EN-60079-11:2012 + (IEC 60079-11:2011)
- Diode polarised and end-of-line resistor compatible
- Dustproof and weatherproof
Technical specifications
| General | ||
|---|---|---|
| Compatibility |
Conventional I.S. zone controllers
|
|
| System support |
Conventional systems
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
24 VDC
|
|
| Operating voltage |
24 VDC
|
|
| Current consumption |
33 mA
|
|
| Sounder | ||
|---|---|---|
| Output level |
<105 dB(A)
|
|
| Selectable tones |
32 (2 stages)
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
102 x 105 (ø x h)
3 x M20 (Cable entries)
|
|
| Net weight |
330 g
|
|
| Colour |
Red
|
|
| Mounting type |
Base mount
|
|
| Mounting position |
Ceiling
Wall
|
|
| Mounting base |
Deep
|
|
| Material |
Flame retardant Polycarbonate
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-40 to +55ºC
|
|
| Relative humidity |
>90% at 20ºC
|
|
| IP rating |
IP66
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RoHS 3
WEEE
|
|
| Certification |
CENELEC/ATEX
CPR
|
|
| Standards |
ATEX (EMT17ATEX0012X) IECEx (EMT 17.0005X)
EN54-3
|
|
Downloads
All downloadsDatasheet
Other EU certificate
CPD / CPR
Certificates
User manual
Application note
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.