KE-IO3101

Excellence series intelligent addressable 1 output unit with isolator
  • Loop powered, saving external supply and installation cost
  • Provides an addressable, potential free change over relay output for 3rd party equipment control
  • EN14637 / BS7273 support for fail to safe operation for emergency doors (as of June '26)
  • Normally Open / Normally Closed programmable for full installation flexibility
  • Magnetic latched output relay to reduce loop loading
View all

Related products

At a glance

General

The innovative Excellence series of intelligent addressable devices offers advanced features for reliability and peace of mind. Coupled with features for ease of installation and maintenance on new fire detection systems, it’s a perfect match for exceptional overall performance.
The Excellence series input/output devices are designed to provide much needed flexibility to input monitoring and output switching. These modules, combined with the powerful features of a Kidde Excellence series addressable CIE, give customers versatility for diverse applications.
The KE-IO3101 is an Excellence series addressable relay output unit with integrated short circuit loop isolation. Powered directly from the Excellence loop, it offers a magnetically latched relay output.

Applications

The KE-IO3101 is designed for controlling building services such as air conditioning and smoke extraction during fire conditions. It is ideal for the control of 3rd party equipment such as door release circuits, emergency shutdown of high risk services such as gas or oil supply valves in boiler rooms. The relay may be programmed to be activated by any single device, groups of devices or all system devices. All types of system input signals can be arranged to operate the KE-IO3101 which can include control panel indicators, zonal outputs, call points or detectors.
The KE-IO3101 may be located anywhere on the Kidde Excellence loop where it occupies only 1 of 128 available addresses. Housed in a low profile molding, the interface is designed to clip directly onto a standard DIN rail fixing or be installed in a suitable wall mount housing. It is intended for installation inside the equipment to be switched, thereby offering savings in installation costs compared with long, auxiliary circuit wiring runs from the control panel.

Installation & Maintenance Features

The KE-IO3101 is connected to the CIE via a 2-wire communication loop that carries both power and control data. Tri-Colour LED indicators positioned on the front face of the unit provide the engineer with clear identification of the operational state of the unit, as well as the status of any input and/or output control. Additional manual test facilities on the unit allows local testing without the need for control panel intervention, saving time during installation and commissioning.
Excellence series devices use an advanced digital data communications protocol with extensive error correction algorithms to ensure system reliability.

Details

  • Loop powered, saving external supply and installation cost
  • Provides an addressable, potential free change over relay output for 3rd party equipment control
  • EN14637 / BS7273 support for fail to safe operation for emergency doors (as of June '26)
  • Normally Open / Normally Closed programmable for full installation flexibility
  • Magnetic latched output relay to reduce loop loading
  • Freely programmable to operate from any combination of input triggers
  • DIN or wall mounted for installation flexibility
  • Local test features for ease of validation
  • Local, clear operation status indication for ease of maintenance

Technical specifications

General
Status indication
Tri-coloured LEDs
Compatibility
Kidde Commercial Excellence Systems
Addressing method
DIP Switches
Address range
1 to 128
Electrical
Power supply type
Loop powered
Operating voltage
17 to 29 VDC
Current consumption
250 μA @ 24 VDC (quiescent)
2.5 mA @ 24 VDC (active)
Communication voltage
4 to 11 V (pulsed)
Output
Output quantity
1
Output type and rating
Relay, 2 A @ 30 VDC (resistive load)
Cable specification 0.13 to 3.31 mm² (12 to 26 AWG) shielded/unshielded twisted-pair
Isolation
Type
Negative line break
Loop current
2.5 mA (active)
Series resistance
<0.08 Ω
Switch current
1.05 A (continuous) / 1.4 A (short)
Leakage current
<1 mA
Isolation voltage
14 to 15.5 VDC
Reconnect voltage
14 to 15.5 VDC
Impedance requirements ≤ 32 devices between isolators
Quantity per loop 128
Physical
Physical dimensions
87 x 80 x 26 mm (W x H x D)
Net weight
60 g
Colour
Signal white (RAL 9003)
Mounting type
DIN-rail
Surface mount
Wall mount
Material
PC / ABS
Cable specification
Loop: 0.13 to 3.31 mm² (12 to 26 AWG) shielded/unshielded twisted-pair < 52 Ω , < 500 nF
Environmental
Vandal proof
No
Operating temperature
-22 to +55°C
Storage temperature
-30 to +65°C
Relative humidity
10 to 93% noncondensing
Environment
Indoor
IP rating
IP30
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR
Standards
EN54-17, EN54-18